🔗 Connect Smarter, Control Further — The Analog Gateway You Can't Afford to Miss!
The Taidacent 10/12 Bit AD Multi Channel Converter transforms dual analog signals (4-20mA, 0-5V, 0-10V) into Modbus RTU/TCP data over RS485, featuring industrial-grade protections, configurable communication settings, and a communication range up to 2000 meters, making it an essential module for reliable, long-distance industrial automation.
A**A
Changing Modbus ID
Unit comes with default Modbus ID 1 and Baud rate 4800.To change Modbus ID, write new ID to Holding Register 0X07D0 (default is 1)To change Baud Rate, write 0,1,2 for 2400,4800,9600 to Holding Register 0X07D1 (default is 1)
M**R
Works, but needs better documentation
Using the default values, the module works out of the box, but no instructions are provided to change the slave address or baud rate. Not finding it with an internet search either
T**G
Work great once got the documentation
Simple and working as it should. Seller need to provide the information to setup the device and not only the specification what it can do. Without the information on how to setup the parameter, it will take forever to figure out.Coding: 8-bit binaryData Bit: 8 BitsParity Bit: NoneStop bit: 1Error Checking: CRCBaud rate support: 2400/4800/9600 ****factory default is 4800**to change the baud rate, write to address 0x07D1 (00 for 2400, 01 for 4800, 02 for 9600)Read modbus "holding register command" to read the first 2 register for the data, as simple as that.***seller please update the spec. to include this info.
F**.
Documentation provided
Device setup for reading values i.e. using Modbus ScanDevice ID =1, Data bit 8, Parity bit none, stop bit 1, error checking CRC.Addresses for analog IN1 are 40001or 40065 and for analog IN2 40002 or 40066* connect to RS-485 to Modbus TCP and slap it onto SCADA
H**E
Incomplete- the instructions state that settings can be configured with software but missing
The instructions indicate the modbus ID and baud rate can be set with config software but no software is provided. Jumber settings or downloadable software should be provided to allow configuring these values.
Trustpilot
1 week ago
3 days ago